5. Installer Setup (ISU)


5.1 Accesing ISU

1. Press Menu and buttons for 3 seconds to enter the installer setup menu.

2. With "ISU" displayed, press Select.

3. Press or to change the selected ISU option.

4. Press Select to move to the next ISU, and press Back button to move the previous.

5. To finish and save the selected ISUs, press Home.


5.2 Advanced Setup Options (ISU)

Note: Depending on system settings, not all options may be available.

# ISU

ISU Name

ISU Options (factory default in bold)

120

Scheduling Options

0 = Non-Programmable

2 = 5-2 Programmable

3 = 5-1-1 Programmable

4 = 7-Day Programmable

125

Temperature Indication Scale

0 = Fahrenheit

1 = Celsius

130

Outdoor Sensor (TH6320U / TH6220U only)

0 = None

1 = Wired Outdoor Sensor

200

Heating System Type

1 = Conventional Forced Air Heat

2 = Heat Pump

3 = Radiant Heat

5 = None (Cool Only)

205

Heating Equipment Type

Conventional Forced Air Heat:

1 = Standard Efficiency Gas Forced Air

2 = High Efficiency Gas Forced Air

3 = Oil Forced Air

4 = Electric Forced Air

5 = Hot Water Fan Coil

Heat Pump:

7 = Air to Air Heat Pump

8 = Geothermal Heat Pump

 

Radiant Heat:

9 = Hot Water Radiant Heat

12 = Steam

218

Reversing Valve O/B

0 = O (O/B in Cool)

1 = B (O/B in Heat)

220

Cool Stages/Compressor Stages 200=Conv/200=HP

0, 1, 2

Note: Only 1 compressor stage available on TH6210U model. Only 1 compressor stage available on TH6220U model if configured for heat pump.

221

Heat Stages / Backup Heat Stages

Heat Stages: 1, 2

Backup Heat Stages: 0, 1

230

Fan Control in Heat

1 = Equipment Controls Fan

2 = Thermostat Controls Fan

253

Aux/E terminal control (Fixed to “0” setting on all models except TH6320U)

0 = Drive both Aux & E together

1 = Aux and E independent

255

Backup Heat Source (Heat Pump Only) (TH6320U / TH6220U only)

1 = Electric Forced Air

2 = Gas/Oil Forced Air (or Fossil Forced Air)

256

Emergency Heat Source (TH6320U only)

1 = Electric Forced Air

2 = Gas/Oil Forced Air (or Fossil Forced Air)

260

External Fossil Fuel Kit (TH6320U / TH6220U only)

0 = Thermostat Controls Backup Heat

1 = External Fossil Fuel Kit Controls Backup Heat

300

System Changeover

0 = Manual

1 = Automatic

303

Auto Changeover Differential

0 °F to 5 °F

0.0 °C to 2.5 °C

Note: Differential is NOT deadband. Resideo uses an advanced algorithm that fixes deadband at 0 °F. The differential setting is the minimum number of degrees from set-point needed to switch from the last mode running (heat or cool) to the opposite mode when the thermostat is in auto-changeover. This is more advanced than previous thermostats.

340

Backup Heat Droop

0 = Comfort

2 = 2 °F

3 = 3 °F

4 = 4 °F

5 = 5 °F

6 = 6 °F

7 = 7 °F

8 = 8 °F

9 = 9 °F

10 = 10 °F

11 = 11 °F

12 = 12 °F

13 = 13 °F

14 = 14 °F

15 = 15 °F

Note: 0 (comfort) setting only available if backup heat (ISU#255) is set to Electric.

350

Upstage Timer for Backup Heat

0 = Off

1 = 30 minutes

2 = 45 minutes

3 = 60 minutes

4 = 75 minutes

5 = 90 minutes

6 = 2 hours

7 = 3 hours

8 = 4 hours

9 = 5 hours

10 = 6 hours

11 = 8 hours

12 = 10 hours

13 = 12 hours

14 = 14 hours

16 = 16 hours

355

Compressor Lockout / Balance Point

-- = Off

5 °F to 60 °F (in 5 °F increments)

-15.0 °C to 15.5 °C (in 2.5 °C or 3.0 °C increments)

Note: Use a wired sensor to set compressor lockout / balance point on TH6320U / TH6220

356

Outdoor Lockout Backup Heat

-- = Off

5 °F to 65 °F (in 5 °F increments)

-15.0 °C to 18.5 °C (in 2.5 °C or 3.0 °C increments)

365

Compressor Cycle Rate (Stage 1)

1 - 6

366

Compressor Cycle Rate (Stage 2)

1 - 6

370

Heating Cycle Rate (Stage 1)

1 - 12

371

Heating Cycle Rate (Stage 2)

1 - 12

375

Heating Cycle Rate Auxiliary Heat

1 - 12

378

Heating Cycle Rate Emergency Heat (TH6320U only)

1 - 12

387

Compressor Protection

0 = Off

1 - 5 minutes

425

Adaptive Intelligent Recovery

0 = No

1 = Yes

Note: Adaptive Intelligent Recovery (AIR) is a comfort setting. Heating or cooling equipment will turn on earlier, ensuring the indoor temperature will match the setpoint at the scheduled time.

430

Minimum Cool Setpoint

50 °F to 99 °F (50 °F)

10.0 °C to 37.0 °C (10.0 °C)

431

Maximum Heat Setpoint

40 °F to 90 °F (90 °F)

4.5 °C to 32.0 °C (32.0 °C)

435

Keypad Lockout

Series 0-6 (setting on original T6 models):

0 = None

1 = Partial

2 = Full

 

Series 7 (setting current T6 models):

0 = Disabled

1 = Enabled

 

Note: Due to customer feedback this feature was changed. On series 0-6 thermostats, you can lock out the thermostat from the ISU the same as you can from menu lockout. For series 7 or later, this setting allows the contractor to enable or disable the lockout feature. When disabled, there is no lockout option under menu.

500

Is Indoor Temperature Sensor WIRED to your system? (TH6320U /TH6220U only)

0 = No

1 = Yes

515

Indoor Sensor type (TH6320U / TH6220U only)

0 = 10k

1 = 20k

520

Which Sensors will be used for TEMPERATURE Control? (Multiple Sensors are Averaged) TH6320U /TH6220U only)

1 = Thermostat Only

2 = Wired Only

3 = Average

702

Number of Air Filters

0 - 2

711

Air Filter 1 Replacement Reminder

0 = Off

1 = 10 Run Time Days

2 = 20 Run Time Days

3 = 30 Run Time Days

4 = 45 Run Time Days

5 = 60 Run Time Days

6 = 90 Run Time Days

7 = 120 Run Time Days

8 = 150 Run Time Days

9 = 30 Calendar Days

10 = 45 Calendar Days

11 = 60 Calendar Days

12 = 75 Calendar Days

13 = 3 Calendar Months

14 = 4 Calendar Months

15 = 5 Calendar Months

16 = 6 Calendar Months

17 = 9 Calendar Months

18 = 12 Calendar Months

19 = 15 Calendar Months

712

Air Filter 2 Replacement Reminder

0 = Off

1 = 10 Run Time Days

2 = 20 Run Time Days

3 = 30 Run Time Days

4 = 45 Run Time Days

5 = 60 Run Time Days

6 = 90 Run Time Days

7 = 120 Run Time Days

8 = 150 Run Time Days

9 = 30 Calendar Days

10 = 45 Calendar Days

11 = 60 Calendar Days

12 = 75 Calendar Days

13 = 3 Calendar Months

14 = 4 Calendar Months

15 = 5 Calendar Months

16 = 6 Calendar Months

17 = 9 Calendar Months

18 = 12 Calendar Months

19 = 15 Calendar Months

1400

Backlighting

0 = On Demand

1 = Continuous

Note: Common wire needed for continuous.

1401

Backlight brightness

1 - 5

Note: Only displayed if continuous backlight selected.

1410

Clock Format

12 / 24

1415

Daylight Saving Time

0 = Off

1 = On

1420

Temperature Display Offset

-3 to 3F (0)

-1.5 to 1.5C (0)

ISU#: 120

Scheduling Options

0 = Non-Programmable

2 = 5-2 Programmable

3 = 5-1-1 Programmable

4 = 7-Day Programmable

ISU#: 125

Temperature Indication Scale

0 = Fahrenheit

1 = Celsius

ISU#: 130

Outdoor Sensor (TH6320U / TH6220U only)

0 = None

1 = Wired Outdoor Sensor

ISU#: 200

Heating System Type

1 = Conventional Forced Air Heat

2 = Heat Pump

3 = Radiant Heat

5 = None (Cool Only)

ISU#: 205

Heating Equipment Type

Conventional Forced Air Heat:

1 = Standard Efficiency Gas Forced Air

2 = High Efficiency Gas Forced Air

3 = Oil Forced Air

4 = Electric Forced Air

5 = Hot Water Fan Coil

 

Heat Pump:

7 = Air to Air Heat Pump

8 = Geothermal Heat Pump

 

Radiant Heat:

9 = Hot Water Radiant Heat

12 = Steam

ISU#: 218

Reversing Valve O/B

0 = O (O/B in Cool)

1 = B (O/B in Heat)

ISU#: 220

Cool Stages / Compressor Stages 200=Conv / 200=HP

0, 1, 2

Note: Only 1 compressor stage available on TH6210U model. Only 1 compressor stage available on TH6220U model if configured for heat pump.

ISU#: 221

Heat Stages / Backup Heat Stages

Heat Stages: 1, 2

Backup Heat Stages: 0, 1

ISU#: 230

Fan Control in Heat

1 = Equipment Controls Fan

2 = Thermostat Controls Fan

ISU#: 253

Aux/E terminal control (Fixed to “0” setting on all models except TH6320U)

0 = Drive both Aux & E together

1 = Aux and E independent

ISU#: 255

Backup Heat Source (Heat Pump Only) (TH6320U / TH6220U only)

1 = Electric Forced Air

2 = Gas/Oil Forced Air (or Fossil Forced Air)

ISU#: 256

Emergency Heat Source (TH6320U only)

1 = Electric Forced Air

2 = Gas/Oil Forced Air (or Fossil Forced Air)

ISU#: 260

External Fossil Fuel Kit (TH6320U / TH6220U only)

0 = Thermostat Controls Backup Heat

1 = External Fossil Fuel Kit Controls Backup Heat

ISU#: 300

System Changeover

0 = Manual

1 = Automatic

ISU#: 303

Auto Changeover Differential

0 °F to 5 °F

0.0 °C to 2.5 °C

Note: Differential is NOT deadband. Resideo uses an advanced algorithm that fixes deadband at 0 °F. The differential setting is the minimum number of degrees from set-point needed to switch from the last mode running (heat or cool) to the opposite mode when the thermostat is in auto-changeover. This is more advanced than previous thermostats.

ISU#: 340

Backup Heat Droop

0 = Comfort

2 = 2 °F

3 = 3 °F

4 = 4 °F

5 = 5 °F

6 = 6 °F

7 = 7 °F

8 = 8 °F

9 = 9 °F

10 = 10 °F

11 = 11 °F

12 = 12 °F

13 = 13 °F

14 = 14 °F

15 = 15 °F

Note: 0 (comfort) setting only available if backup heat (ISU 255) is set to Electric.

ISU#: 350

Upstage Timer for Backup Heat

0 = Off

1 = 30 minutes

2 = 45 minutes

3 = 60 minutes

4 = 75 minutes

5 = 90 minutes

6 = 2 hours

7 = 3 hours

8 = 4 hours

9 = 5 hours

10 = 6 hours

11 = 8 hours

12 = 10 hours

13 = 12 hours

14 = 14 hours

16 = 16 hours

ISU#: 355

Compressor Lockout / Balance Point

-- = Off

5 °F to 60 °F (in 5 °F increments)

-15.0 °C to 15.5 °C (in 2.5 °C or 3.0 °C increments)

Note: Use a wired sensor to set compressor lockout / balance point on TH6320U / TH6220U.

ISU#: 356

Outdoor Lockout Backup Heat

-- = Off

5 °F to 65 °F (in 5 °F increments)

-15.0 °C to 18.5 °C (in 2.5 °C or 3.0 °C increments)

ISU#: 365

Compressor Cycle Rate (Stage 1)

1 - 6

ISU#: 366

Compressor Cycle Rate (Stage 2)

1 - 6

ISU#: 370

Heating Cycle Rate (Stage 1)

1 - 12

ISU#: 371

Heating Cycle Rate (Stage 2)

1 - 12

ISU#: 375

Heating Cycle Rate Auxiliary Heat

1 - 12

ISU#: 378

Heating Cycle Rate Emergency Heat (TH6320U only)

1 - 12

ISU#: 387

Compressor Protection

0 = Off

1 - 5 minutes

ISU#: 425

Adaptive Intelligent Recovery

0 = No

1 = Yes

Note: Adaptive Intelligent Recovery (AIR) is a comfort setting. Heating or cooling equipment will turn on earlier, ensuring the indoor temperature will match the setpoint at the scheduled time.

ISU#: 430

Minimum Cool Setpoint

50 °F to 99 °F (50 °F)

10.0 °C to 37.0 °C (10.0 °C)

ISU#: 431

Maximum Heat Setpoint

40 °F to 90 °F (90 °F)

4.5 °C to 32.0 °C (32.0 °C)

ISU#: 435

Keypad Lockout

Series 0-6 (setting on original T6 models):

0 = None

1 = Partial

2 = Full Series

 

7 (setting current T6 models):

0 = Disabled

1 = Enabled

 

Note: This feature has been changed in response to customer feedback. On Series 0-6 thermostats, you can lock out the thermostat from the ISU, the same as you can from menu Lockout. For Series 7 or later, this setting allows the contractor to enable or disable the Lockout feature. When disabled, there is no Lockout option under Menu.

ISU#: 500

Is Indoor Temperature Sensor WIRED to your system? (TH6320U / TH6220U only)

0 = No

1 = Yes

ISU#: 515

Indoor Sensor type (TH6320U/TH6220U only)

0 = 10k

1 = 20k

ISU#: 520

Which Sensors will be used for TEMPERATURE Control? (Multiple Sensors are Averaged) (TH6320U / TH6220U only)

1 = Thermostat Only

2 = Wired Only

3 = Average

ISU#: 702

Number of Air Filters

0 - 2

ISU#: 711

Air Filter 1 Replacement Reminder

0 = Off

1 = 10 Run Time Days

2 = 20 Run Time Days

3 = 30 Run Time Days

4 = 45 Run Time Days

5 = 60 Run Time Days

6 = 90 Run Time Days

7 = 120 Run Time Days

8 = 150 Run Time Days

9 = 30 Calendar Days

10 = 45 Calendar Days

11 = 60 Calendar Days

12 = 75 Calendar Days

13 = 3 Calendar Months

14 = 4 Calendar Months

15 = 5 Calendar Months

16 = 6 Calendar Months

17 = 9 Calendar Months

18 = 12 Calendar Months

19 = 15 Calendar Months

ISU#: 712

Air Filter 2 Replacement Reminder

0 = Off

1 = 10 Run Time Days

2 = 20 Run Time Days

3 = 30 Run Time Days

4 = 45 Run Time Days

5 = 60 Run Time Days

6 = 90 Run Time Days

7 = 120 Run Time Days

8 = 150 Run Time Days

9 = 30 Calendar Days

10 = 45 Calendar Days

11 = 60 Calendar Days

12 = 75 Calendar Days

13 = 3 Calendar Months

14 = 4 Calendar Months

15 = 5 Calendar Months

16 = 6 Calendar Months

17 = 9 Calendar Months

18 = 12 Calendar Months

19 = 15 Calendar Months

ISU#: 1400

Backlighting

0 = On Demand

1 = Continuous

Note: Common wire needed for continuous.

ISU#: 1401

Backlighting Brightness

1 - 5

Note: Only displayed if continuous backlight selected.

ISU#: 1410

Clock Format

12 / 24

ISU#: 1415

Daylight Saving Time

0 = Off

1 = On

ISU#: 1420

Temperature Display Offset

-3 to 3F (0)

-1.5 to 1.5C (0)